Railway Cables | ||||||||||||
450/750V LSZH Track Feeder Cables
to EME-SP-14-025/SE908
Application
The cables can provide the 450/750 volt DC supply from Traction Substations and Track Paralleling Huts to conductor rails, negative cable connections and where appropriate bonding.
Standards
● EME SP 14 025 (replaced by LUL 1-108 and Metronet MR SE908)
● UNE 21123
Construction
Conductors
Stranded tinned copper conductors to IEC 60228 class 2 or 5.
Insulation
EPR.
Sheath
LSZH sheathed with yellow stripe.
Electrical Characteristics at 20℃
Nominal Conductor Cross Section | mm² |
500 |
935 |
Maximum DC Conductor Resistance | Ω/km |
0.0361 |
0.0194 |
Voltage Rating | KV |
0.45/0.75 |
Mechanical and Thermal Properties
Minimum Bending Radius: 8×OD
Temperature Range: -25℃ to +85℃ (during operation); -10℃ to +70℃ (during installation)
Dimensions And Weight
Cable Code |
No. of cores& Nominal Conductor Cross Sectional Area No.×mm² |
No. & Nominal Diameter of Strands No/mm |
Nominal Sheath Thickness mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
RF14025-DZ1-U(AS)-450/750V-1G500 | 1×500 | 91/2.65 | 8.5 | 54.0 | 7185 |
RF14025-DZ1-U(AS)-450/750V-1G935 | 1×935 | 169/2.65 | 9.5 | 65.0 | 11749 |